How big a mini split does the room need?

Start at 20 BTU per square foot, adjust for the room, then pick the head size that covers the result. One size up is fine; two sizes up wastes money and short-cycles. An undersized unit never catches up on the hottest day.

Size a room

Size one room here.

The same rules as the tables below and the builder: 20 BTU per square foot, adjusted for ceiling height, insulation and sun.

450 sq ftabout 21 × 21 ft8 ft ceilingaverage insulationsunny
sq ft
Ceiling height
Insulation
Sun

Windows beyond two, more than two people, a kitchen and your climate add to the load. The builder asks for each of them.

Recommended 12K head, estimated load 9,900 BTU.

Estimated load

9,900Btu/h

  1. 450 sq ft× 20 BTU9,000
  2. 8 ft ceiling× 1.009,000
  3. Average insulation× 1.009,000
  4. Sunny or west-facing+10%9,900
12K

A 12,000 BTU headCovers about 400 to 600 sq ft

Size every room in the builder

It takes a few minutes. Nothing is ordered until you check out.

Head sizes

Head sizes and the rooms they cover.

Room sizes assume 8 ft ceilings, average insulation and average sun (20 to 30 BTU per sq ft). Each size links to the units in it.

Head sizes and the rooms they cover
SizeRoom size
6,000 BTU200 to 300 sq ft
9,000 BTU300 to 450 sq ft
12,000 BTU400 to 600 sq ft
15,000 BTU500 to 750 sq ft
18,000 BTU600 to 900 sq ft
24,000 BTU800 to 1,200 sq ft
30,000 BTU1,000 to 1,500 sq ft
36,000 BTU1,200 to 1,800 sq ft
48,000 BTU1,600 to 2,400 sq ft
54,000 BTU1,800 to 2,700 sq ft
60,000 BTU2,000 to 3,000 sq ft

Adjustments

What moves the number.

Apply each one that fits the room to the 20 BTU per square foot starting point. The builder applies the same rules.

Load adjustments
ConditionAdjustment
Ceiling above 8 ft× height ÷ 8
Poor insulation+15%
Good insulation−10%
Sunny or west-facing+10%
Shaded−10%
Each window beyond two+500 BTU
Each person beyond two+600 BTU
Kitchen+4,000 BTU
Hot climate (FL, TX, AZ, Gulf states)+10%
Cold climate (northern states)+15%

Worked example

A 400 sq ft room needs an 18K head.

A living room with 9 ft ceilings, average insulation, a west-facing wall with four windows and an open kitchen. The square footage alone suggests 9,000 BTU. The adjustments almost double it.

Several rooms: one condenser or several?

A multi-zone condenser drives two to six heads and keeps the outside of the house tidy, but every head runs off one compressor and the manufacturer limits the total connected capacity. Separate single-zone systems keep running if one fails and are simpler to install. The builder shows both kinds side by side when they fit.

The math

  1. 400 sq ft× 20 BTU8,000
  2. 9 ft ceiling× 9 ÷ 89,000
  3. West-facing glass+10%9,900
  4. Two windows beyond two+1,00010,900
  5. Open kitchen+4,00014,900
Room load14,900BTU

Pick the 18,000 BTU head. 12,000 would run flat out on the hottest day and still fall behind.

Size every room in the builder

Vaulted ceilings, sunrooms or very old houses: call and we size it by hand.